Faq

Frequently asked questions

Got questions? Our Technical Support Manager responds to the most frequent ones


Ιf I do not press any button while reading an error for 3 sec, then i can see the day and time it occurred.

By pressing the enter button we enter the error menu. We see the most recent error.    In order to see older errors we should press the down arrow.

First, I turn in maintenance mode and then I press the upper or down arrow

In order to enable maintenance, we press once the revision button on the board's screen. Before this, the screen should show the floor.

To return to normal mode, we press for 5 sec the same button until the led which is above it is turned off.

  1. check the safety chain's leakage relay
  2. check the safety chain's fuse
  3. check that the yellow cable (neutral 110VAC) is properly connected to the sk3 board

  1. check three phase supervisor
  2. check switch S1 if it is activated
  3. UPS must also be connected to MRL panels
  4. connect the unique neutral to both terminal 4N and terminal X2:N
  5. we check if we have 230VAC between the terminals T - 4N

We need to connect to the single-phase input of the elevator panel, neutral that does not pass through the leakage relay or we need to connect to the single-phase input of the elevator panel, a phase passing through the three-phase leakage relay

We connect the unique neutral to both terminal 4N and terminal X2:N

The green led of the three phase supervisor must be on